Input sensor calibration :
a. Thermocouple : Chromael-Alumel (Cr/Al)-up to 1200ºC
Platinum-Platinum-Rhodium (Pt/Pt-Rh)-up to 1600ºC
b. RTD : Resistance Temperature Detector (Pt-100) temperature & upto 400ºC

Indication Accuracy : ±1% of FSD
Compensation : Cold junction compensation automatic thermocouple models

Relay Status : Relay energized or heating ( or cooling)
Relay output : One chance over relay contact 5A/230V rating.
Control Action : ON-OFF or time proportional
Control Version : single set point or Dual set point
Sensor break protection : Relay turns off in case of sensor break
Power Supply : 230V AC±15%, 50 Hz
Indication : Mains ON, Relay ON and thermocouple
Max, ambient temp. : 55ºC

Installation : The RTD sensor should be connected to instrument by proper cables to minimum due to cable resistance. For Thermocouple sensor, compensating cable of proper be used.


Modal Series 100 200 300 300
Size (in mm) 96x96 72x72 48x96 96x48
Cutout (in mm) 92x92 68x68 44x92 92x44
Depth (in mm) 100 120 (75 for Indicators) 120 120
Mounting Flush panel mounting with side clamps fixed panel
Ordering Information For better selection or model, range and calibration
Model No. : Specify possible better as
Type of sensor : Pt-100, Cr/Al or 13%

Specifications are subject to change due to continuous product improvement